X20ST4492 B&R Electronic Components

X20ST4492 on Powermatic Associates
B&R

Part#:X20ST4492

Manufacturer:B&R

Category:Electronic Components

Product Lifecycle:Active

Only 2 left in stock. Order Now!

Jul 20, 2025

Product description

X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C, T, resolution 0.1°C, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated compensation of terminal temperatu

Product Details

  • I/O module
    2x 2 safe analog inputs for thermocouples, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated terminal temperature compensation, integrated temperature sensor in terminal block X20TB5E
  • Linearization method
    Internal
  • Pitch
    25+0.2 mm
  • System requirements Automation Studio
    3.0.81.15 or later
  • Blackout mode Standalone mode
    No
  • Certifications DNV
    Temperature: A (0 - 45°C); Humidity: B (up to 100%); Vibration: A (0.7 g); EMC: B (bridge and open deck)
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD
    <1*10-4
  • Basic accuracy Type K: NiCr-Ni
    1.81°C
  • Basic accuracy Voltage
    78 µV
  • Common-mode rejection DC
    >70 dB
  • Measurement range Pt100
    -200.0 to 850.0°C
  • Safety-related accuracy per channel Pt1000
    8.93°C
  • Temperature Storage
    -40 to 85°C
  • Measurement range Sensor temperature Type T: Cu-CuNi
    -270.0 to 400.0°C
  • Max. I/O cycle time
    2 ms
  • Max. gain drift
    0.013 %/°C
  • Installation elevation above sea level
    0 to 2000 m, no limitation
  • System requirements mapp Technology Package
    mapp Safety 5.7.0 or later
  • Electrical isolation Channel - Bus
    Yes
  • Certifications LR
    ENV1
  • Certifications EAC
    Yes
  • Measurement range Voltage
    ±65 mV
  • Basic accuracy Type T: Cu-CuNi
    0.74°C
  • Max. offset drift Voltage
    1.69 µV per °C
  • Safety-related accuracy per channel Type T: Cu-CuNi
    30.82°C
  • Input filter Cutoff frequency
    500 Hz first-order
  • Relative humidity Storage
    5 to 95%, non-condensing
  • Measurement range Sensor temperature Type J: Fe-CuNi
    -210.0 to 1200.0°C
  • Status indicators
    I/O function per channel, operating state, module status
  • Input filter
    First-order low-pass filter / cutoff frequency 500 Hz
  • System requirements Automation Runtime
    3.00 or later
  • System requirements Safety Release
    1.4 or later
  • Electrical isolation Channel - Channel
    No
  • Certifications ATEX
    Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL
    SIL 3
  • Basic accuracy Type J: Fe-CuNi
    1.41°C
  • Max. offset drift Type N: NiCrSi-NiSi
    0.0471°C per °C
  • Safety-related accuracy per channel Type J: Fe-CuNi
    35.25°C
  • Max. offset drift Pt100
    0.0525°C per °C
  • Relative humidity Operation
    5 to 95%, non-condensing
  • Measurement range Sensor temperature Type R: PtRh13-Pt
    -50.0 to 1768.0°C
  • B&R ID code
    0xB419
  • Insulation voltage between channel and bus
    500 VDC
  • Diagnostics Module run/error
    Yes, using LED status indicator and software
  • Variant
    Type thermocouple
  • Certifications UL
    cULus E115267; Industrial control equipment
  • EN ISO 13849-1:2015 Category
    Cat. 4
  • Basic accuracy Type N: NiCrSi-NiSi
    1.73°C
  • Max. offset drift Type R: PtRh13-Pt
    0.1455°C per °C
  • Safety-related accuracy per channel Type R: PtRh13-Pt
    134.54°C
  • Basic accuracy Pt1000
    0.53°C
  • Relative humidity Transport
    5 to 95%, non-condensing
  • Measurement range Sensor temperature Type K: NiCr-Ni
    -270.0 to 1372.0°C
  • Sensor standard
    EN 60584
  • Measurement current
    262 µA ±5%
  • Degree of protection per EN 60529
    IP20
  • Voltage range
    24 VDC -15% / +20%
  • Certifications Functional safety
    cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
  • EN ISO 13849-1:2015 DC
    >94%
  • Resolution Sensor temperature
    1 LSB = 0.1°C
  • Max. offset drift Type J: Fe-CuNi
    0.0297°C per °C
  • Safety-related accuracy per channel Type N: NiCrSi-NiSi
    51.81°C
  • Max. offset drift Pt1000
    0.0053°C per °C
  • Temperature Derating
    See section "Derating".
  • Measurement range Sensor temperature Type C: WRe5-WRe26
    0 to 2320.0°C
  • Terminal temperature compensation
    Internal / External
  • Common-mode range
    ±4 V within channel pair, ±50 V between 2 channel pairs
  • System requirements SafeDESIGNER
    2.81 or later
  • Blackout mode Scope
    Module
  • Power consumption Internal I/O
    1.2 W
  • Certifications HazLoc
    cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
  • EN ISO 13849-1:2015 MTTFD
    2200 years
  • Measurement range Max. internal resistance of source during voltage measurement
    20 Ω
  • Max. offset drift Type K: NiCr-Ni
    0.0427°C per °C
  • Common-mode rejection 50 Hz
    >70 dB
  • Safety-related accuracy per channel Voltage
    2080 µV
  • Mounting orientation Horizontal
    Yes
  • Temperature Transport
    -40 to 85°C
  • Measurement range Sensor temperature Type N: NiCrSi-NiSi
    -270.0 to 1300.0°C
  • Output format
    SAFEINT
  • Permissible input signal
    Max. ±1 V
  • Note
    The following characteristic values apply only to the use of input channel pairs.; Assessing the channels from a safety point of view when they are used individually is not possible.
  • Blackout mode Function
    Module functionality
  • Certifications UKCA
    Yes
  • Certifications ABS
    Yes
  • EN ISO 13849-1:2015 Mission time
    Max. 20 years
  • Resolution Voltage
    1 LSB = 2 µV
  • Max. offset drift Type S: PtRh10-Pt
    0.1637°C per °C
  • Safety-related accuracy per channel Type S: PtRh10-Pt
    150.90°C
  • Temperature sensor resolution Pt100
    1 LSB = 0.1°C
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Per channel
    <1*10-9
  • Temperature Operation Horizontal mounting orientation
    0 to 60°C
  • Filter time
    Configurable between 1 and 66.7 ms
  • Crosstalk between channels
    ≤70 dB
  • Nominal voltage
    24 VDC
  • Electrical isolation Channel pair - Channel pair
    Yes
  • EN ISO 13849-1:2015 PL
    PL e
  • Basic accuracy Type S: PtRh10-Pt
    3.10°C
  • Max. offset drift Type C: WRe5-WRe26
    0.1068°C per °C
  • Safety-related accuracy per channel Type C: WRe5-WRe26
    111.36°C
  • Temperature sensor resolution Pt1000
    1 LSB = 0.1°C
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless
    <1*10-14 * Number of openSAFETY packets per hour
  • Temperature Operation Vertical mounting orientation
    0 to 50°C
  • Digital converter resolution
    24-bit
  • Max. line resistance
    5 Ω
  • Quantity
    2 safe input channel pairs
  • Certifications CE
    Yes
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SFF
    >90%
  • Basic accuracy Type C: WRe5-WRe26
    3.48°C
  • Terminal temperature compensation Accuracy of internal terminal temperature
    15°C at static temperatures and during safe operation
  • Measurement range Pt1000
    -200.0 to 850.0°C
  • Safety-related accuracy per channel Pt100
    12.60°C
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired
    Negligible
  • Conversion procedure
    Sigma-delta
  • Max. line length
    50 m
  • Diagnostics Inputs
    Yes, using LED status indicator and software
  • Power consumption Bus
    0.25 W
  • Certifications KR
    Yes
  • Certifications KC
    Yes
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT)
    20 years
  • Basic accuracy Type R: PtRh13-Pt
    3.10°C
  • Max. offset drift Type T: Cu-CuNi
    0.0335°C per °C
  • Safety-related accuracy per channel Type K: NiCr-Ni
    47.62°C
  • Basic accuracy Pt100
    1.89°C
  • Mounting orientation Vertical
    Yes
  • Measurement range Sensor temperature Type S: PtRh10-Pt
    -50.0 to 1768.0°C

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



Manufacturer warranty

X20ST4492 B&R

Get a quick Quote!

Request a quote, and we will send you price within minutes.

Stock:

2

Select Qty:

Average response time: 11 minutes

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

Compare X20ST4492 with other Electronic Components products

I/O module

Linearization method

Pitch

System requirements Autom...

Blackout mode Standalone ...

Certifications DNV

IEC 61508:2010,; IEC 6151...

Basic accuracy Type K: Ni...

Basic accuracy Voltage

Common-mode rejection DC

Selected product

X20ST4492
2 in stock
X20ST4492
B&R

X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C...

I/O module2x 2 safe analog inputs for ...

Linearization methodInternal

Pitch25+0.2 mm

System requirements Automation Studio3.0.81.15 or later

Blackout mode Standalone modeNo

Certifications DNVTemperature: A (0 - 45°C); H...

IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD<1*10-4

Basic accuracy Type K: NiCr-Ni1.81°C

Basic accuracy Voltage78 µV

Common-mode rejection DC>70 dB

X20AT6402
5 in stock
X20AT6402
B&R

X20 temperature input module, 6 thermocouple inputs, type J, K, N, S, B, R, resolution 0.1°C

I/O module6 inputs for thermocouples

Linearization methodInternal

Pitch-

System requirements Automation Studio-

Blackout mode Standalone mode-

Certifications DNV-

IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD-

Basic accuracy Type K: NiCr-Ni-

Basic accuracy Voltage-

Common-mode rejection DC-

X20AI4622
12 in stock
X20AI4622
B&R

X20 analog input module, 4 inputs, ±10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution, co...

I/O module4 analog inputs ±10 V or 0 t...

Linearization method-

Pitch-

System requirements Automation Studio-

Blackout mode Standalone mode-

Certifications DNV-

IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD-

Basic accuracy Type K: NiCr-Ni-

Basic accuracy Voltage-

Common-mode rejection DC-

About the manufacturer

B&R

Powermatic Associates is an authorized B&R distributor, bringing you cutting-edge automation technology from one of the world's leading innovators in industrial automation. B&R, a member of the ABB Group, excels in providing advanced solutions that enhance productivity and efficiency across various industries. With a comprehensive portfolio of products, B&R offers modular hardware and flexible sof...

Recently viewed products

Relevant products

FAQ

2 in stock

X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C, T, resolution 0.1°C, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated compensation of terminal temperatu

Similar products from: Electronic Components

What can I help you find today?

Recommended parts