X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C, T, resolution 0.1°C, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated compensation of terminal temperatu
Product Details
- I/O module 2x 2 safe analog inputs for thermocouples, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated terminal temperature compensation, integrated temperature sensor in terminal block X20TB5E
- Linearization method Internal
- Pitch 25+0.2 mm
- System requirements Automation Studio 3.0.81.15 or later
- Blackout mode Standalone mode No
- Certifications DNV Temperature: A (0 - 45°C); Humidity: B (up to 100%); Vibration: A (0.7 g); EMC: B (bridge and open deck)
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD <1*10-4
- Basic accuracy Type K: NiCr-Ni 1.81°C
- Basic accuracy Voltage 78 µV
- Common-mode rejection DC >70 dB
- Measurement range Pt100 -200.0 to 850.0°C
- Safety-related accuracy per channel Pt1000 8.93°C
- Temperature Storage -40 to 85°C
- Measurement range Sensor temperature Type T: Cu-CuNi -270.0 to 400.0°C
- Max. I/O cycle time 2 ms
- Max. gain drift 0.013 %/°C
- Installation elevation above sea level 0 to 2000 m, no limitation
- System requirements mapp Technology Package mapp Safety 5.7.0 or later
- Electrical isolation Channel - Bus Yes
- Certifications LR ENV1
- Certifications EAC Yes
- Measurement range Voltage ±65 mV
- Basic accuracy Type T: Cu-CuNi 0.74°C
- Max. offset drift Voltage 1.69 µV per °C
- Safety-related accuracy per channel Type T: Cu-CuNi 30.82°C
- Input filter Cutoff frequency 500 Hz first-order
- Relative humidity Storage 5 to 95%, non-condensing
- Measurement range Sensor temperature Type J: Fe-CuNi -210.0 to 1200.0°C
- Status indicators I/O function per channel, operating state, module status
- Input filter First-order low-pass filter / cutoff frequency 500 Hz
- System requirements Automation Runtime 3.00 or later
- System requirements Safety Release 1.4 or later
- Electrical isolation Channel - Channel No
- Certifications ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL SIL 3
- Basic accuracy Type J: Fe-CuNi 1.41°C
- Max. offset drift Type N: NiCrSi-NiSi 0.0471°C per °C
- Safety-related accuracy per channel Type J: Fe-CuNi 35.25°C
- Max. offset drift Pt100 0.0525°C per °C
- Relative humidity Operation 5 to 95%, non-condensing
- Measurement range Sensor temperature Type R: PtRh13-Pt -50.0 to 1768.0°C
- B&R ID code 0xB419
- Insulation voltage between channel and bus 500 VDC
- Diagnostics Module run/error Yes, using LED status indicator and software
- Variant Type thermocouple
- Certifications UL cULus E115267; Industrial control equipment
- EN ISO 13849-1:2015 Category Cat. 4
- Basic accuracy Type N: NiCrSi-NiSi 1.73°C
- Max. offset drift Type R: PtRh13-Pt 0.1455°C per °C
- Safety-related accuracy per channel Type R: PtRh13-Pt 134.54°C
- Basic accuracy Pt1000 0.53°C
- Relative humidity Transport 5 to 95%, non-condensing
- Measurement range Sensor temperature Type K: NiCr-Ni -270.0 to 1372.0°C
- Sensor standard EN 60584
- Measurement current 262 µA ±5%
- Degree of protection per EN 60529 IP20
- Voltage range 24 VDC -15% / +20%
- Certifications Functional safety cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
- EN ISO 13849-1:2015 DC >94%
- Resolution Sensor temperature 1 LSB = 0.1°C
- Max. offset drift Type J: Fe-CuNi 0.0297°C per °C
- Safety-related accuracy per channel Type N: NiCrSi-NiSi 51.81°C
- Max. offset drift Pt1000 0.0053°C per °C
- Temperature Derating See section "Derating".
- Measurement range Sensor temperature Type C: WRe5-WRe26 0 to 2320.0°C
- Terminal temperature compensation Internal / External
- Common-mode range ±4 V within channel pair, ±50 V between 2 channel pairs
- System requirements SafeDESIGNER 2.81 or later
- Blackout mode Scope Module
- Power consumption Internal I/O 1.2 W
- Certifications HazLoc cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
- EN ISO 13849-1:2015 MTTFD 2200 years
- Measurement range Max. internal resistance of source during voltage measurement 20 Ω
- Max. offset drift Type K: NiCr-Ni 0.0427°C per °C
- Common-mode rejection 50 Hz >70 dB
- Safety-related accuracy per channel Voltage 2080 µV
- Mounting orientation Horizontal Yes
- Temperature Transport -40 to 85°C
- Measurement range Sensor temperature Type N: NiCrSi-NiSi -270.0 to 1300.0°C
- Output format SAFEINT
- Permissible input signal Max. ±1 V
- Note The following characteristic values apply only to the use of input channel pairs.; Assessing the channels from a safety point of view when they are used individually is not possible.
- Blackout mode Function Module functionality
- Certifications UKCA Yes
- Certifications ABS Yes
- EN ISO 13849-1:2015 Mission time Max. 20 years
- Resolution Voltage 1 LSB = 2 µV
- Max. offset drift Type S: PtRh10-Pt 0.1637°C per °C
- Safety-related accuracy per channel Type S: PtRh10-Pt 150.90°C
- Temperature sensor resolution Pt100 1 LSB = 0.1°C
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Per channel <1*10-9
- Temperature Operation Horizontal mounting orientation 0 to 60°C
- Filter time Configurable between 1 and 66.7 ms
- Crosstalk between channels ≤70 dB
- Nominal voltage 24 VDC
- Electrical isolation Channel pair - Channel pair Yes
- EN ISO 13849-1:2015 PL PL e
- Basic accuracy Type S: PtRh10-Pt 3.10°C
- Max. offset drift Type C: WRe5-WRe26 0.1068°C per °C
- Safety-related accuracy per channel Type C: WRe5-WRe26 111.36°C
- Temperature sensor resolution Pt1000 1 LSB = 0.1°C
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
- Temperature Operation Vertical mounting orientation 0 to 50°C
- Digital converter resolution 24-bit
- Max. line resistance 5 Ω
- Quantity 2 safe input channel pairs
- Certifications CE Yes
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SFF >90%
- Basic accuracy Type C: WRe5-WRe26 3.48°C
- Terminal temperature compensation Accuracy of internal terminal temperature 15°C at static temperatures and during safe operation
- Measurement range Pt1000 -200.0 to 850.0°C
- Safety-related accuracy per channel Pt100 12.60°C
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired Negligible
- Conversion procedure Sigma-delta
- Max. line length 50 m
- Diagnostics Inputs Yes, using LED status indicator and software
- Power consumption Bus 0.25 W
- Certifications KR Yes
- Certifications KC Yes
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT) 20 years
- Basic accuracy Type R: PtRh13-Pt 3.10°C
- Max. offset drift Type T: Cu-CuNi 0.0335°C per °C
- Safety-related accuracy per channel Type K: NiCr-Ni 47.62°C
- Basic accuracy Pt100 1.89°C
- Mounting orientation Vertical Yes
- Measurement range Sensor temperature Type S: PtRh10-Pt -50.0 to 1768.0°C
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
X20ST4492 Related Documents
Similar products from: B&R Electronic Components
Manufacturer warranty
X20ST4492 B&R
Get a quick Quote!
Request a quote, and we will send you price within minutes.
Stock:
Select Qty:
Average response time: 11 minutes
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
Compare X20ST4492 with other Electronic Components products
I/O module
Linearization method
Pitch
System requirements Autom...
Blackout mode Standalone ...
Certifications DNV
IEC 61508:2010,; IEC 6151...
Basic accuracy Type K: Ni...
Basic accuracy Voltage
Common-mode rejection DC
Selected product

X20ST4492
B&R
X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C...
I/O module2x 2 safe analog inputs for ...
Linearization methodInternal
Pitch25+0.2 mm
System requirements Automation Studio3.0.81.15 or later
Blackout mode Standalone modeNo
Certifications DNVTemperature: A (0 - 45°C); H...
IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD<1*10-4
Basic accuracy Type K: NiCr-Ni1.81°C
Basic accuracy Voltage78 µV
Common-mode rejection DC>70 dB
About the manufacturer
Powermatic Associates is an authorized B&R distributor, bringing you cutting-edge automation technology from one of the world's leading innovators in industrial automation. B&R, a member of the ABB Group, excels in providing advanced solutions that enhance productivity and efficiency across various industries. With a comprehensive portfolio of products, B&R offers modular hardware and flexible sof...
Recently viewed products
Relevant products
FAQ
2 in stock
X20 safe temperature input module, 2x 2 safe analog inputs for thermocouples, Type: J, K, N, S, R, C, T, resolution 0.1°C, 1x 2 safe analog inputs for PT100/PT1000 sensors, channel pairs galvanically isolated, integrated compensation of terminal temperatu
Similar products from: Electronic Components
What can I help you find today?